EasyManua.ls Logo

RFL Electronics RFL 9300 - Figure 3-23. Open Conductor with One Single-Line-To-Ground Fault (OC;SLG)

RFL Electronics RFL 9300
553 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
(OPEN)
SLG
LOCAL REMOTE
Figure 3-23. Open conductor with one single-line-to-ground fault (OC/SLG)
3.15.3 GROUND STRONG-FEED
If the load current is 0.5 ampere or more, ground strong-feed will usually operate and provide sensitive protec-
tion for the OC/SLG condition. This is equivalent to a fault current caused by about 220 ohms of fault resistance
@ 138 kV, using 1200:5 CT's.
A phasor analysis of ground strong-feed operation is shown in Figures 3-24 and 3-25. From this analysis, sev-
eral observations can be made about ground strong-feed operation:
1. The 3I
0
component due to the high-resistance SLG fault is in-phase or 180 degrees out-of-phase with
the 3I
0
due to the open conductor. This is because both are "watt-flow" (resistive) currents. The open
conductor effect relates to load current (resistive) on the affected phase. The SLG effect relates to the
resistive effect of the ground fault resistance.
2. The 3I
0
magnitude due to the high-resistance SLG fault is a direct function of the ground fault resistance
(R
G
).
3. If the SLG is on the load sending end
side of the open conductor (Fig. 3-24), the 3I
0
currents due to the
open conductor and the SLG are subtractive
. This creates a region of net 3I
0
on the SLG side that may be
below 0.5 amperes. This prevents ground strong-feed operation for certain R
G
values.
4. If the SLG is on the load receiving end
side of the open conductor (Fig. 3-25), the 3I
0
currents due to
the open conductor and the SLG are additive
. This assures ground strong-feed tripping for all R
G
values
of 220 ohms or less @ 138 kV, using 1200:5 CT's.
The OC/2-SLG and OC/SLG conditions will both be correctly detected by the RFL 9300. The RFL 9300's degree
of sensitivity depends upon the value of the ground fault resistance (R
G
), load current, and which side of the
open is shorted to ground.
RFL 9300 RFL Electronics Inc.
August 25, 2000 3 - 26 (973) 334-3100

Table of Contents