6.5.5 READING PARAMETER SETTINGS
The "D" command tells the RFL 9300 to send a list of all parameter settings to your terminal. This list of settings
is called the "read settings" menu.
Format: 9300>D [ENTER]
Typical read settings menus appear in Figures 6-11 through 6-14. All settings described in Section 4 of this
manual are shown, but you can't change the displayed values. To change these values, you will have to enter
the programming mode. (See para. 6.4.4 for more information.) The programming mode is password-protected,
so only authorized persons can change the RFL 9300's parameter settings.
#
020
022
024
026
028
030
032
034
036
038
041
044
048
050
121
122
141
999
9300>
PARAMETER
Phase Bias
Bias Control
Bias/Ground Dly
F. D. Ground
Phase O/C Bkup
Phase TOC
(2)
Ph TOC Curve
Ground TOC
(3)
Gd TOC Curve
Overhd/Undergd
Comms Alm Dly
Beeper
Comms Mode
Guard/Trip
Current Time
Reset Disp. Alrm
Slctv Pole RL
System Label
SETTING
.500 amps
Disable
.05/.05 sec
1.0 Amp
31.875 Amps
Disable
N/A
Disable
N/A
Overhead
Disable
Disable
Auto
Disable
09:25:23
No
Disable
Gen1
#
021
023
025
027
029
031
033
035
037
040
042
046
049
120
140
145
PARAMETER
Ground Bias
Ground Delay
F. D. Phase
Backup
(1)
Ground O/C Bkup
Ph TOC Pickup
Ph TOC Dial
Gd TOC Pickup
Gd TOC Dial
Stub Bus
(1)
DC Offset Filter
Transmit Addr 1
Active Channel
Current Date
Single Pole
Trip Release
SETTING
1.500 amps
Enable
8.0 Amps
Enable
31.000 Amps
N/A
N/A
N/A
N/A
Inactive
Enable
4079
1
08/16/00
Active
CS+TRIP
Figure 6-11. Typical read settings menu for two-terminal single-pole mode
RFL 9300 RFL Electronics Inc.
January 30, 2002 6-41 (973) 334-3100