EasyManua.ls Logo

RFL Electronics RFL 9300 - Figure 3-20. Zero-Sequence Current Flows through Transformer; Figure 3-21. Typical Tapped Line Application

RFL Electronics RFL 9300
553 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 3-20. Zero-sequence current flows through transformer
3.14.1 CALCULATIONS FOR LOW-SIDE FAULTS
Figure 3-21 shows a typical tapped line application. Assume that the high-side three-phase fault current under
minimum system conditions is 15,000 amperes primary (which is equal to 31.25 amperes secondary). To con-
duct a worst-case analysis of this application, a maximum system will be considered (all generators and all lines
in service). The equivalent system impedance will be ignored, so the high-voltage bus at the tap will be treated
as an "infinite" source. It is also assumed that all the limiting impedance for the low-side fault is due to the trans-
former impedance. This will introduce a safety factor of about 10-percent into the calculations.
Figure 3-21. Typical tapped line application
RFL 9300 RFL Electronics Inc.
August 25, 2000 3 - 22 (973) 334-3100

Table of Contents