EasyManua.ls Logo

RFL Electronics RFL 9300 - Figure 8-2. Test Connections Simulating an Internal A-G Fault

RFL Electronics RFL 9300
553 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.2.3.4 INTERNAL FAULTS
The following procedures simulate three types of internal faults: A-G, A-B, and three-phase.
8.2.3.4.1 Internal A-G Faults
This procedure demonstrates "SFT" (Strong-Feed Trip) and "UHS" (Ultra-High Speed Trip). SFT requires test
currents of at least 0.5 Arms. UHS operates whenever the test current reaches +12 Apeak for 2 ms, and the
terminal does not have a peak reading that is more negative than the peak Blocking Level (BL). The value of the
local station CT control current required to block a UHS signal received from the remote station(s), referred to
as the UHS bias value, is a function of the phase bias setting.
BL = – (11 amperes – bias amperes)peak (minimum value is 7.5A peak)
The equation applies over a limited range of phase bias settings. The range allowed is from 1-2.5 Arms. If the
value was less than 1 amp it would already have failed the range test. If the phase bias setting >2.5 Arms the
value used for the equivalent peak phase bias setting in the above equation is 3.5 A (peak). Any value greater
than this would reduce the blocking current level below 7.5 A (peak) which approaches the level of normal load
current (5 Arms max). It is not desirable to have normal load current levels block UHS since this would essen-
tially disable the function.
Example: For a bias setting of 3 amperes rms (4.2A peak):
BL = – (11 amperes – 4.2 amperes) = – 6.8A peak
BL = – 7.5 amperes peak (minimum value)
UHS is usually about 5 ms faster than SFT.
1. Connect the equipment as shown in Figure 8-2.
This creates an "internal" current line-up for Phase A and ground.
AC
CURRENT
SOURCE
TB4
TB5
A
C
T
A
C
T
TB6
TB7
A
C
T
A
C
T
1
1 1 1
2
2
2
2
3I
0
I
C
I
B
I
A
Figure 8-2. Test connections simulating an internal A-G fault
RFL 9300 RFL Electronics Inc.
October 20, 2004 8 - 12 (973) 334-3100

Table of Contents