EasyManua.ls Logo

RFL Electronics RFL 9300 - Figure 7-2. Test Connections Simulating an External A-G Fault

RFL Electronics RFL 9300
553 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.4.3 EXTERNAL A-G FAULTS
This procedure will prove out the ac current measurement function, the fault detector response, and stability
during external faults.
1. Connect a single-phase ac current source to both RFL 9300s. (See Figure 7-2).
This simulates an external A-G fault. At the left RFL 9300, test current is injected into
the Phase A polarity terminal and the 3I
0
non-polarity terminal. At the right RFL 9300,
the polarities are opposite.
The system external connection diagrams in Section 5 of this manual show the 3I
0
cur-
rent connected to the non-polarity terminal of the ground ACT (rear-panel terminal TB4-
2). This effectively inverts the polarity of the residual current relative to the phase cur-
rents. This technique provides tripping on each half-cycle for ground faults. By invert-
ing the polarity of 3I
0
relative to I
A
, the test circuit of Figure 7-2 follows this technique.
AC
CURRENT
SOURCE
TB4
TB5
A
C
T
A
C
T
TB6 TB7
A
C
T
A
C
T
3I
0
I
C
I
B
I
A
1 1 1 1
2 2 2 2
TB4
TB5
A
C
T
A
C
T
TB6
TB7
A
C
T
A
C
T
3I
0
I
C
I
B
I
A
1 1 1 1
2 2 2 2
LEFT TERMINAL RIGHT TERMINAL
Figure 7-2. Test connections simulating an external A-G fault
2. Vary the magnitude of the ac test current. Place either RFL 9300 in the READ display mode, and ver-
ify that the Phase A and 3I
0
currents are the same value as the test current.
The currents can be checked by viewing the following parameters:
Local Phase A current Parameter #5 (LOC IA)
Local 3I
0
current Parameter #8 (LOC 3I0)
Remote Phase A current Parameter #9 (REM1 IA)
Remote 3I
0
current Parameter #12 (REM1 3I0)
RFL 9300 RFL Electronics Inc.
October 20, 2004 7 - 8 (973) 334-3100

Table of Contents