EasyManua.ls Logo

RFL Electronics RFL 9300 - List of Illustrations

RFL Electronics RFL 9300
553 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RFL 9300 RFL Electronics Inc.
September 5, 2007 ix (973) 334-3100
LIST OF ILLUSTRATIONS
Figure 2-1. Block diagram, RFL 9300 Charge Comparison System (two terminal)............................................................... 2
Figure 2-2. Logic diagram, composite fault detector ............................................................................................................ 14
Figure 2-3. Logic diagram, strong-feed trips (for 2- and 3- terminal systems)..................................................................... 15
Figure 2-4. Differential Characteristics for 9300 in 2- and 3- terminal modes ..................................................................... 16
Figure 2-5. Logic diagram, weak-feed trip (for 2- and 3- terminal systems) ........................................................................ 18
Figure 2-6. Logic diagram, switch-into-fault with communications (2- and 3- terminal systems) ....................................... 19
Figure 2-7. Logic diagram, ultra high-speed trip .................................................................................................................. 20
Figure 2-8. Logic diagram for open conductor and loss of load algorithm........................................................................... 21
Figure 2-9. Logic diagram, stub-bus applications................................................................................................................. 23
Figure 2-10. Logic diagram, switch-into-fault without communications.............................................................................. 25
Figure 2-11. Logic diagram, trip seal-in................................................................................................................................28
Figure 2-12. Logic diagram, DTT trip seal-in....................................................................................................................... 29
Figure 3-1. Voltage inversion ................................................................................................................................................. 2
Figure 3-2. Phase unbalance ................................................................................................................................................... 2
Figure 3-3. High source-to-line impedance ratio .................................................................................................................... 3
Figure 3-4. Effect of infeed/outfeed........................................................................................................................................ 4
Figure 3-5. Strong bus tie........................................................................................................................................................ 4
Figure 3-6. High-resistance ground fault with heavy through-load, causing an outfeed condition ........................................ 5
Figure 3-7. Polar diagram,....................................................................................................................................................... 5
Figure 3-8. Prefault load subtraction eliminates generator angles .......................................................................................... 7
Figure 3-9. Currents before pre-fault subtraction.................................................................................................................... 8
Figure 3-10. Currents after pre-fault subtraction..................................................................................................................... 8
Figure 3- 11. Operation of the RFL 9300’s UHS circuit during an internal fault................................................................. 10
Figure 3-12. Operation of the RFL 9300’s UHS circuit during and external fault ............................................................... 10
Figure 3-13. Saturated main current transformers during close-in internal fault .................................................................. 11
Figure 3-14. External fault with very severe CT saturation at one end................................................................................. 13
Figure 3-15. Weak infeed application ................................................................................................................................... 15
Figure 3-16. Double line-to-ground (DLG) fault.................................................................................................................. 17
Figure 3-17. Sub-bus protection............................................................................................................................................ 19
Figure 3-18. Typical tapped line application......................................................................................................................... 20
Figure 3-19. Transformer in-rush.......................................................................................................................................... 21
Figure 3-20. Zero-sequence current flows through transformer ........................................................................................... 22
Figure 3-21. Typical tapped line application......................................................................................................................... 22
Figure 3-22. Open conductor with two single-line-to-ground faults (OC/2-SLG) ............................................................... 25
Figure 3-23. Open conductor with one single-line-to-ground fault (OC/SLG)..................................................................... 26
Figure 3-24. Phasor analysis of ground strong-feed operation, based on a load current of 0.5 amperes or more, with the
SLG fault occurring on the load sending end side of the open conductor ..................................................................... 27
Figure 3-25. Phasor analysis of ground strong-feed operation, based on a load current of 0.5 amperes or more, with the
SLG fault occurring on the load receiving end side of the open conductor ................................................................... 28
Figure 3-26. Open conductor without single-line-to-ground fault........................................................................................ 29
Figure 3-27. Possible miscoordination of loss-of-load plus Zone 2 timer ............................................................................ 30
Figure 5-1. Mounting dimensions of RFL 9300 chassis without single pole option............................................................... 3
Figure 5-2. Mounting dimensions of RFL 9300 chassis with single pole option.................................................................... 4
Figure 5-3. Rear view, typical RFL 9300 Charge Comparison System .................................................................................. 6
Figure 5-4. Electrical connections between RFL 9300 and current transformers on protected line ....................................... 7
Figure 5-5. Electrical connections between RFL 9300 with optional test switch chassis and current transformers on
protected line.................................................................................................................................................................... 8
Figure 5-6. Overview of a typical 9300 two-terminal installation .......................................................................................... 9
Figure 5-7. Overview of a typical RFL 9300 three-terminal installation................................................................................ 9

Table of Contents