EasyManua.ls Logo

RFL Electronics RFL 9300 - Saturated Main Current Transformers; Figure 3-13. Saturated Main Current Transformers During Close-In Internal Fault

RFL Electronics RFL 9300
553 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.9 SATURATED MAIN CURRENT TRANSFORMERS
The main current transformers are particularly subject to saturation on close-in internal faults. A general rule of
thumb is that the CTs used in relay applications will reproduce the primary current waveform with acceptable
accuracy for at least a half-cycle or more. The UHS algorithm is designed to execute during this interval. This
provides high-speed clearing for this condition.
3.9.1 INTERNAL FAULT CALCULATION
Two separate calculations should be made to select the proper CT's: one for "SLG" (single-line-to-ground)
faults, and one for three-phase faults. Use the following formula for SLG faults:
V
KPS
= I
SLG
x R
2W
x TF
G
where
V
KPS
= Kneepoint voltage of the CT's B-H curve for worst-case SLG fault.
I
SLG
= Maximum expected SLG fault current (symmetrical, in secondary amperes rms).
R
2W
= "Two-way" secondary cable resistance, in ohms.
TF
G
= "Transient factor" for ground faults. This is equal to (1 + X
L
/R) where (L/R) is the primary system
time constant.
Figure 3-13. Saturated main current transformers during close-in internal fault
RFL 9300 RFL Electronics Inc.
August 25, 2000 3 - 11 (973) 334-3100

Table of Contents