k. Press .248 ENT.
l. After a few seconds, the word "ALARM" will flash on the top line of the display, and typically
the numbers "16 or 17", “34 or 35” and "46" will appear on the bottom line. The numbers
may be different due to factory test settings. (A complete list of alarm codes appears in Ta-
ble 6-4 of this section.)
m. This completes the programming of the remote 1 transmit addresses.
8. Turn on the remote 2 RFL 9300 by placing the POWER switch on the power supply module to the ON
(up) position, and observe the following:
a. All three indicators on the front of the power supply will light, indicating that the power sup-
ply is functioning normally. The words "Please Wait" will appear on the display. Red alarm
indicators on the 93A SV and 93A PC modules will light, and the beeper will sound.
b. If the beeper is annoying, it can be shut off by disabling parameter #44 (audio beeper en-
able/disable) by using the PROGRAM mode, as described in para. 6.4.4 later in this sec-
tion.
c. A green light will illuminate on the display controller (EN/GN = enable/green). This means
that trip is enabled.
d. After a few seconds, the word "ALARM" will flash on the top line of the display, and typically
the numbers "16" and "17" will appear on the bottom line. The numbers may be different
due to factory test settings. (A complete list of alarm codes appears in Table 6-4 of this
section.)
e. The remote RFL 9300 will remain in this state as long as remote 1 and remote 2 transmit
addresses have not been programmed.
9. Program the remote 2 RFL 9300 transmit address as follows:
a. On the display module keypad press the ENT key three times to get into the
PROGRAM/DISABLE screen.
b. Press the 8 key to get into the PROGRAM/ENABLE screen.
c. Press the ENT key to enter the SEC CODE screen. (The 9300 is asking the operator for
the security code)
d. Press .248 ENT. This will get you into the PH BIAS screen in programming mode.
e. Go to the XMT ADD1 screen by doing one of the following:
- Press the ENT key repeatedly until you get to the XMT ADD1 screen.
- Hold the ENT key down to scroll to the XMT ADD1 screen.
- Enter .46 ENT to get to the XMT ADD1 screen.
f. Press 8 to scroll up, or press 0 to scroll down to the desired transmit address for the re-
mote RFL 9300. Holding the key down will accelerate the rate at which the numbers
change. After about 5 seconds the numbers will scroll by 100’s. If you press 9 it will cancel
the current setting and go back to the previous setting. The transmit address is user se-
lectable from 0016 to 4079. This address gets transmitted to the corresponding local unit
for address verification. The sum of the local and remote addresses must equal 4095. For
example, if the local unit transmit address is set to 4000, then the remote unit transmit ad-
dress must be set to 0095.