RFL 9300 RFL Electronics Inc.
January 30, 2002 6-38 (973) 334-3100
032 - SV LCCT B Local Alarm From Supervisor Module: Local Charge Comparison Trip (calcu-
lated without active fault detector) Phase B.
033 - SV LCCT C Local Alarm From Supervisor Module: Local Charge Comparison Trip (calcu-
lated without active fault detector) Phase C.
034 - SV Parallel Port Local Alarm From Supervisor Module: Parallel Port Alarm.
035 - SV S/W Mismatch Local Alarm From Supervisor Module: Software Mismatch Alarm.
037 - SV/R1 Config Err General Alarm From Remote 1 Supervisor Module: Configuration Mismatch of pro-
grammable jumpers.
045 - Open Conductor Local Alarm: Open conductor alarm.
046 - System Comms Remote/General Alarm: Communications to/from remote station are failed or
impaired.
047 - SV/R2 Config Err General Alarm From Remote 2 Supervisor Module: Configuration Mismatch of pro-
grammable jumpers.
054 – SPT General Single-Pole logic general alarm. Problem on SP chassis detected by 93B SV.
Problem with (or no) serial message sent by SP logic.
055 – PH A SG POLE CS Phase A single-pole trip alarm: Phase A dc trip current sensed for more than
500ms by SP logic, or Phase A dc trip current sensed without a Phase A trip
signal being issued.
056 – PH B SG POLE CS Phase B single-pole trip alarm: Phase B dc trip current sensed for more than
500ms by SP logic, or Phase B dc trip current sensed without a Phase B trip
signal being issued.
057 – PH C SG POLE CS Phase C single-pole trip alarm: Phase C dc trip current sensed for more than
500ms by SP logic, or Phase C dc trip current sensed without a Phase C trip
signal being issued.
060 – PH A Cntrlr Phase A Controller general alarm: Fail bus test with 93B SV, bad communica-
tions with 93B SV, excessive channel delay detected, or system clock out of
spec.
061 – PH B Cntrlr Phase B Controller general alarm: Fail bus test with 93B SV, bad communica-
tions with 93B SV, excessive channel delay detected, or system clock out of
spec.
062 – PH C Cntrlr Phase C Controller general alarm: Fail bus test with 93B SV, bad communica-
tions with 93B SV, excessive channel delay detected, or system clock out of
spec.
063 – 3I0 Cntrlr Phase 3I0 Controller general alarm: Fail bus test with 93B SV, bad communications
with 93B SV, excessive channel delay detected, or system clock out of spec.