TERMINAL BLOCK OUTPUT CONNECTIONS:
ALARM OUTPUTS: RECLOSE BLOCK OUTPUTS:
TB8-1 LOCAL ALARM N.C. TB9-1 RECLOSE BLOCK +
TB8-2 LOCAL ALARM N.O. TB9-2 RECLOSE BLOCK -
TB8-3 LOCAL ALARM COM
TB8-4 COMM ALARM N.C.
TB8-5 COMM ALARM N.O.
TB8-6 COMM ALARM COM
TERMINAL BLOCK INPUT CONNECTIONS:
DTT INPUTS:
TB9-3 DTT +
TB9-4 DTT
89B INPUTS:
TB9-5 89B +
TB9-6 89B
JUMPERS: J1, J2, J3, J4 (104775-5 only)
With J1 and J3 installed, and with J2 and J4 removed, the module will operate at 48 Volts.
With J2 and J4 installed, and with J1 and J3 removed, the module will operate at 125 Volts.
With J1, J2, J3 and J4 removed, the module will operate at 250 Volts.
JUMPERS: J1, J2, J3, J4 (104775-7 only)
With J1 and J3 installed, and with J2 and J4 removed, the module will operate at 48 Volts.
With J2 and J4 installed, and with J1 and J3 removed, the module will operate at 110 Volts.
With J1, J2, J3 and J4 removed, the module will operate at 220 Volts.
JUMPERS: J5 and J6 (104775-5, 104775-6 and 104775-7)
Used to wet the contacts of circuits that activate the module inputs. These jumpers should not be
inserted with station battery voltages in excess of 125 Volts.
RFL 9300 RFL Electronics Inc.
May 5, 2002 21 - 3 (973) 334-3100