24.2.3 TEST POINTS
TP1 TRIP_A_IN A logic low trip command for phase A from the RFL 9300
TP2 SV_DAT Serial data line to the supervisor module
TP3 A_SENSE_1 Logic high when trip current is sensed in trip relay 1 for phase A
TP4 A_SENSE_2 Logic high when trip current is sensed in trip relay 2 for phase A
TP5 TRIP_A_OUT Processed trip command signal which will close relays K3 – K8
TP6 GROUND Signal ground
TP7 TRIP_B_IN A logic low trip command for phase B from the RFL 9300
TP8 SPARE Spare test point
TP9 B_SENSE_1 Logic high when trip current is sensed in trip relay 1 for phase B
TP10 B_SENSE_2 Logic high when trip current is sensed in trip relay 2 for phase B
TP11 TRIP_B_OUT Processed trip command signal which will close relays K11 – K16
TP12 GROUND Signal ground
TP13 TRIP_C_IN A logic low trip command for phase C from the RFL 9300
TP14 SP_CHAS Logic low used by supervisor module to detect presence of single pole chassis
TP15 C_SENSE_1 Logic high when trip current is sensed in trip relay 1 for phase C
TP16 C_SENSE_2 Logic high when trip current is sensed in trip relay 2 for phase C
TP17 TRIP_C_OUT Processed trip command signal which will close relays K19 – K24
TP18 GROUND Signal ground
TP19 TRIP_DISABLE Trip disable command from RFL 9300. Logic high blocks tripping.
TP20 DISP_DATA Serial data line from the RFL 9300 display module to the single pole chassis
TP21 CLK_IN 3.584 mHz local oscillator clock
TP22 DISP_CLK Clock burst from 9300 display module to single pole chassis
TP23 SYS_CLK 2kHz system clock from 9300 used for serial communications to supervisor module
TP24 +15V +15 Vdc
TP25 -15V -15Vdc
TP26 +5V +5Vdc
TP27 TP Spare test point for factory use only
TP28 TP Spare test point for factory use only
TP29 TP Spare test point for factory use only