EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Page 1075

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.11
Date Code 20171006 Instruction Manual SEL-400 Series Relays
Reporting
Oscillography
.CFG File
The .CFG file contains data such as sample rates, number of channels, line fre-
quency, channel information, and transformer ratios (see Figure ). A <CR><LF>
follows each line. If control inputs or control outputs are not available because of
board loading and configuration, the relay does not report these inputs and out-
puts in the analog and digital sections of the .CFG file.
Relay 1 Date: 02/02/2011 Time: 14:11:21.000
Station A Serial Number: 2010265004
Event: ABG T Location: 59.61 (mi) From: LOCAL FLM: TW Time Source: HIRIG
Event Number: 10121 Shot 1P: 0 Shot 3P: 0 Freq: 59.99 Group: 1
Targets:
Breaker 1: CLOSED
Breaker 2: OPEN
PreFault: IA IB IC IG 3I2 VA VB VC V1mem
MAG(A/kV) 200 200 200 1 1 133.946 133.938 133.941 133.935
ANG(DEG) -0.7 -120.5 119.4 -51.7 -88.7 0.0 -119.9 120.2 0.1
Fault:
MAG(A/kV) 2200 2200 2200 7 376 133.937 133.926 133.957 133.933
ANG(DEG) -0.7 -120.6 119.5 -102.0 -83.5 0.0 -119.9 120.2 0.1
87 Differential Currents
PreFault: IA IB IC IQ IG
MAG(pu) 0.00 0.00 0.00 0.00 0.00
ANG(DEG) 0.0 0.0 0.0 0.0 0.0
Fault:
MAG(pu) 0.00 0.00 0.00 0.00 0.00
ANG(DEG) 0.0 0.0 0.0 0.0 0.0
Summary Event
Information
SET_G1.TXT
[INFO]
RELAYTYPE=SEL-411L
FID=SEL-411L-X136-V0-Z001001-D20110114
BFID=SLBT-4XX-R205-V0-Z001002-D20100128
PARTNO=0411L0X6X1B6BCXH5C4E4XX
[IOBOARDS]
INT4_E, , , 24, 8, 0, 0, 1
CFSINT8, , , 8, 8, 0, 0, 2
[G1]
"SID","Station A"
"RID","Relay 1"
"NUMBK",2
"BID1","Breaker 1"
"BID2","Breaker 2"
"NFREQ",60
.
.
.
"AR197",
"AR198",
"AR199",
"AR200",
Relay Settings
Figure 9.5 Sample COMTRADE .HDR Header File
Station A,FID=SEL-411L-1-R100-V0-Z001001-D20110311,1999
Relay Information (1999 = COMTRADE Standard)
398,14A,384D
398 = sum of analogs and digitals
14A = total number of analog channels
384D = total number of digital points
a
1,IAW,A,,A,0.324059,0,0,-32767,32767,200.0,1,P
2,IBW,B,,A,0.324059,0,0,-32767,32767,200.0,1,P
3,ICW,C,,A,0.324059,0,0,-32767,32767,200.0,1,P
4,IAX,A,,A,0.324059,0,0,-32767,32767,200.0,1,P
5,IBX,B,,A,0.324059,0,0,-32767,32767,200.0,1,P
6,ICX,C,,A,0.324059,0,0,-32767,32767,200.0,1,P
7,VAY,A,,kV,0.032406,0,0,-32767,32767,2000.0,1,P
8,VBY,B,,kV,0.032406,0,0,-32767,32767,2000.0,1,P
9,VCY,C,,kV,0.032406,0,0,-32767,32767,2000.0,1,P
10,VAZ,A,,kV,0.032406,0,0,-32767,32767,2000.0,1,P
11,VBZ,B,,kV,0.032406,0,0,-32767,32767,2000.0,1,P
12,VCZ,C,,kV,0.032406,0,0,-32767,32767,2000.0,1,P
13,VDC1,,,V,0.011178,-0.000000,0,-32767,32767,1,1,P
14,VDC2,,,V,0.011178,-0.000000,0,-32767,32767,1,1,P
14 Analog Channels
COMTRADE .CFG Configuration File Data

Table of Contents

Related product manuals