14.34
SEL-400 Series Relays Instruction Manual Date Code 20171006
ASCII Command Reference
Command Description
If the device supports IEC 61850 and the IEC 61850 protocol is enabled, the ID
command will display the following additional information.
➤ iedName: the IED name (e.g., SEL-411L_OtterTail)
➤ type: the IED type (e.g., SEL-411L)
➤ configVersion: the CID file configuration version (e.g.,
ICD-411L-R100-V0-Z001001-20060512)
➤ LIB61850ID: an eight-character code indicating the IEC 61850
library version within the product
A sample ID command response from the relay (with IEC 61850 enabled) is
shown in Figure 14.6.
IRIG
The IRIG command directs the relay to use the next available demodulated
IRIG-B time code to update the relay internal clock. For information on the IRIG
time mode, see IRIG-B Timekeeping on page 11.1.
NOTE: Not all SEL-400 series relays
support the IRIG command.
The IRIG command was originally provided in the relay as a testing aid. The
IRIG command was used to update the relay internal clock with the IRIG-B time
value without waiting for the 30-second confirmation time delay.
There is no longer a 30-second confirmation time delay—the relay uses the IRIG
time source as soon as it determines that the signal is valid, a process that may
take several seconds. Once the IRIG signal is verified, the relay clock is updated
once per second. The IRIG command is still available, but is no longer neces-
sary. To check IRIG status, use the TIME Q command instead—see TIME Q
Command on page 11.8.
If the relay has no valid IRIG-B time code at the rear panel, or if the TIME Q
command reports a relay time source other than IRIG or HIRIG, the relay
responds to the IRIG command with the following error message,
IRIG-B DATA
ERROR
. See the TIME command for more information.
=ID <ENTER>
"FID=SEL-451-5-R319-V0-Z024013-D20170608","0916"
"BFID=SLBT-4XX-R209-V0-Z001002-D20150130","097C"
"CID=85F4","0264"
"DEVID=Relay 1","0467"
"DEVCODE=40","030B"
"PARTNO=04515415XC4X4H60X0XXX","07B3"
"SERIALNO=1234567890","0517"
"CONFIG=11102200","03EA"
"SPECIAL=000000","03CE"
"iedName=SEL_451_1","05CD"
"type=SEL_451","044C"
"configVersion=ICD-451-R301-V0-Z316006-D20170130","0D1C"
"LIB61850ID=9048BE8A","04EA"
=
Figure 14.6 Sample ID Command Response From Ethernet Card
Table 14.79 IRIG Command
Command Description Access Level
IRIG Lock the relay internal clock to the IRIG-B time code input. 1, B, P, A, O, 2