17.27
Date Code 20171006 Instruction Manual SEL-400 Series Relays
IEC 61850 Communication
IEC 61850 Configuration
Step 1. Open Architect.
Step 2. Click on the Settings Link tab, and then click on Create Settings
Link.
Step 3. Select the settings file and then press OK.
Step 4. Select which settings to embed in the CID file. You can also save a
local CID file with settings by clicking on Save CID with Settings.