3.13
Date Code 20171006 Instruction Manual SEL-400 Series Relays
Basic Relay Operations
Checking Relay Status
c. Select the Data Speed, Data Bits, Stop Bits, Parity, and RTS/
CTS that match the relay settings.
The defaults are 9600, 8, 1, None, and Off, respectively.
d. Click OK to update the QuickSet communications parameters
and connect to the relay.
e. Confirm that the Communications Status bar at the bottom of the
QuickSet window says
Connected.
Step 2. Confirm that you have loaded the correct passwords in QuickSet.
a. Enter your Access Level 1 password in the Level One Password
text box, and your Access Level 2 password in the Level Two
Password text box.
b. Click OK to accept changes and close the dialog box.
Step 3. Click Tools in the top toolbar and select the HMI menu to start the
QuickSet operator interface.
Step 4. Click the Status button of the HMI tree view (see Figure 3.9).
QuickSet displays the relay status with a display similar to that in
Figure 3.9.
Figure 3.8 QuickSet Communication Parameters and Password Entry