REV 0, June 1005 Page 237
Operation Manual SUPREMA
11. Technical Data
- individual function keys for horn acknowledgement and alarm reset
- plain-text messages for alarms and errors at the sampling points
- graphic display of alarm and error states (LED field)
- bar graphs of measurement values
- display of system status (common LEDs for alarms, errors)
- system clock (RTC), optional connection to a wireless clock
- 2 x RS 232 (RS 485 optional), electrically isolated (laptop/printer interface)
Technical Data
Operating voltage feed (3 x 24 VDC): 14 ... 32 VDC
Operating current:
without backlighting: 100 mA
with backlighting: 200 mA
Temperature range: 5 °C ... 40 °C
Humidity: 0 ...90 % relative humidity
noncondensing
Plug connector: 40-channel ribbon cable
Dimensions: 107.5 x 211 mm
Weight: 365 g
11.2.4 MGO 10 General Output Unit
Order No.: 10022750
Function
40 driver outputs for relays + LEDs (24 VDC/0.3 A)
Technical Data
Operating voltage feed (3 x 24 VDC): 14 ...32 V
Operating current logic: 50 mA
Total load current, switching outputs: 12 A
Nominal switching voltage: 24 VDC
Nominal switching current: 0.3 A
Maximum driver IC limit data
(8 outputs per driver)
- output current: 500 mA
(all outputs ON, per output)
- output current: 1 A
(1 output ON)
- total current of all outputs of
one driver IC: 4 A
Temperature range: 5 °C ... 40 °C
Humidity: 0 ... 90 % relative humidity
noncondensing
Plug connector: 96-channel VG terminal strip
(pre-mating contacts for power supply)
Dimensions: 100 x 160 mm
Weight: 115 g