REV 0, June 2005Page 186
Operation Manual SUPREMA
6. Startup
6.6 Completing Startup
To check the correctness of all the completed adjustments, it is recommended that all the
inputs be tested with test gas. Verify that the correct alarm is triggered and that the correct
relay driver output is actuated. Keep a record of this test.
Startup is complete after a successful final check of the SUPREMA system and of the completed
installation and calibration procedures. Now the external alarm and warning systems can be
connected.
Warning: To guarantee the unambiguity of catalytic combustion sensor operation
it must be made sure (e.g. by check with hand-held test instruments) each time
before turning on the sensors and the system that the environmental atmosphere
to be monitored by the sensors is free of combustible gases.