REV 0, June 2005Page 240
Operation Manual SUPREMA
11. Technical Data
11.2.9 MPI 10 HL8101 Passiv Input Unit
Order No.: 10024276
Function
- power source for passive sensors (24 VDC)
- supply module for HL sensors
- sensor current, 100 ...400 mA
- prepares the Ux bridge signal
Technical Data
Operating voltage feed: 19.2 ... 32 V
Operating current: 240 mA, maximum
Maximum load: 36 ohms
(at operating voltage of 19.2 V and
sensor current of 210 mA)
Setting range, constant current: 100 ... 230 mA
Setting range, zero point: 820 ohms ± 50 ohms (semiconductor resistor)
Setting range, sensitivity: 24 ... 1100 mV
Temperature range: 5 °C ... 40 °C
Humidity: 0 ... 90 % relative humidity
noncondensing
Dimensions: 46 x 24 mm
Weight: 12 g
11.2.10 MPI 10 HL8113 Passiv Input Unit
Order No.: 10024280
Function
- power source for passive sensors (24 VDC)
- supply module for HL sensors
- sensor current, 100 ... 400 mA
- prepares the Ux bridge signal
Technical Data
Operating voltage feed: 19.2 ... 32 V
Operating current: 240 mA, maximum
Maximum load: 36 ohms
(at operating voltage of 19.2 V and
sensor current of 210 mA)
Setting range, constant current: 100 ... 230 mA
Setting range, zero point: 10 Kohms ± 1 K
Setting range, sensitivity: 24 ... 1100 mV
Temperature range: 5 °C ... 40 °C
Humidity: 0 ... 90 % relative humidity
noncondensing
Dimensions: 46 x 24 mm
Weight: 12 g