REV 0, June 1005 Page 235
Operation Manual SUPREMA
11. Technical Data
11. Technical Data
11.1 System Data
Racks per system: 1–8
Number of inputs - per system: 1–256
- per rack; up to 64
Switching outputs/relay outputs: 0–512, 240 VAC, 3 A, resistive
Analog outputs 0 - 20 mA: 0–256
Operation and Display: 240 x 64 pixel graphics display
cursor keyboard
function keys
Interfaces: 3 x RS232:
- PC operation
- printer
- free
2 x CAN-Bus
System operating voltage: 19.2 V ... 32 VDC
System power supply (3x rendundancy): 3 x 24 VDC
Rack power supply,150 W: 85 ... 265 VAC, 47 ... 63 Hz; 120 ... 330 VDC
- output voltage, rack power supply: 24 VDC
- output current, rack power supply: 6.5 A
System power supply limits to be observed:
- maximum allowable operating current feed (+24 V): 20 A
- maximum rack load current of all MAI cards (+24 V): 10 A
- maximum rack load current of all MGO cards (GND): 12 A
Connectable sensors: - active 4 ... 20 mA, 2-wire
- active 4 ... 20 mA, 3-wire
- active 4 ... 20 mA, 4-wire
- passive 3-wire
- passive 5-wire
- passive 4-wire (semiconductor sensors)
Housing: 19” rack, 3HE
Storage temperature for all parts of the system: -25 °C ... +55 °C
Operating temperature 40 °C max.
Pollution degree 2
Installation category II
Altitude 2000 meters max.