REV 0, June 2005Page 92
Operation Manual SUPREMA
5. Installation
Warning: The area where the modules are installed must be outside of a
hazardos area Zone 0, 1 or 2 and be free of ignitable, explosive or corrosive
gases. Sensor installation at the SUPREMA must be carried out according to
Guideline EN 60079-14.
5.2 Installation, Step by Step
Unpack and inspect the device or its components.
Attention: Follow the instructions for components subject to damage from static
electricity!
Check the suitability of the installation site and the cabling requirements.
Check the current and voltage supply and make sure it is suitable.
Depending on the type of system shipped, install the switch cabinet, or the 19” mounting
rack.
Check the configuration of the modules and reconfigure if necessary.
Install the modules in the 19” mounting rack (unless already installed at the factory).
In the case of expanded systems with more than one 19” mounting rack, connect the
CAN bus or check the connection if it has already been made.
Install the sensors and connect the wiring to the SUPREMA.
Attention: Follow the installation instructions for hazardous areas!
Connect the relay and current outputs to the external devices to be actuated.
Connect the current and voltage supply.
After installation is complete, perform the start-up procedure as instructed in Section 6 “Startup”.
5.2.1 Unpacking
Perform the following steps on receipt of the shipment:
Carefully unpack the device or its components, observing all of the instructions printed on
or accompanying the packaging.
Also inspect the contents of the delivery to determine if any transport damage has
occurred and verify that everything listed in the shipping papers has in fact been
received.
5.2.2 Installation Site
The SUPREMA control unit may be installed only outside of areas subject to the danger of
explosion. The specified temperature and humidity conditions must also be satisfied, and contact
with corrosive substances must be avoided.