REV 0, June 2005Page 314
Operation Manual SUPREMA
12. Sensor Data Sheets
12.33 SUPREMA Sensor Data Sheet DF-9500 EX
Order No.: D0742xxx (xxx-according to the list of components)
The cable screen is connected at the SUPREMA and the DF 9500.
The zener barrier must be installed apart from the explosion range.
Connection module: MCI 10/MCI 20 (active/2-wire/4 ...0 mA linear/current sink)
Sensor
simulation module: 4 ... 20 mA (Order No.: 10030262)
Safety barrier
allowed: SB – 2427, complete (Order No.: 10034362)
Connection data: Supply voltage 14 ... 28 VDC
Supply current 4 ... 30 mA
Maximum power consumption 50 mA
Power consumption 0,4 W (without cable length)
Cable type 2-core, 80 % screened
Maximum burden 500 ohms with Safety barrier
Maximum cable length 2000 m (at 1.5 mm
2
cross section per wire)
Cable diameter 9 ... 13.5 mm
Cross section per wire allowed 0.5 ... 2.5 mm
2
Cable inlet PG 13.5
Conditions for use: Mounting Wall mounting
Ingress protection IP 42 (Sensor) IP 63 (Housing)
Explosion protection II 2G EEx ia IIC T6
Certificate DMT 01 ATEX E 152 X
Temperature min. 20 °C to +40 °C (depending on component)
Humidity min. 20 ... 80 % rel. humidity (depending on
component)