REV 0, June 1005 Page 247
Operation Manual SUPREMA
11. Technical Data
11.2.23 MSI 10 (Switch Input Unit)
Order No.: 10048285
Function
- Power supply for external switches
- Evaluate status of the switches
- The operation with an external power supply is optional.
Technical Data
Internal supply voltage: 19.2 ... 32 V
External supply voltage: 19.2 ... 32 V
External battery reverse polarity protection: Yes
Operating current: max. 30 mA
Output voltage: max. 15 V
Output current: max. 8 mA
Temperature range: 5 °C ... 40 °C
Humidity: 0 ... 90 % relative humidity
noncondensing
Dimensions: 46 x 24 mm
Weight: 8 g
11.2.24 MAT-TS 320 Flammable/Toxic Adapter
Order No. Flammable: 10049234
Order No. Toxic: 10049235
Function
- Terminal connectors for gas detectors
Technical Data
No. of measure gas detectors: 8
No. of terminals per gas detector: Flammable: 3
Toxic: 2
Maximum wire cross section: 2,5 mm
2
Temperature range: 5 °C ... 40 °C
Humidity: 0 ... 90 % relative humidity
noncondensing
Dimensions: 155 x 90 x 60 mm
Weight: 200g
11.2.25 MAT-TS 330 Fire Input (Qatar Version)*
Order No.: 10049236
Function
- Terminals for fire detectors, push-button switches, smoke detectors
* With regard to fire and smoke detection, the SUPREMA has not been evaluated to any Canadian standard by
a third party agency.