REV 0, June 1005 Page 243
Operation Manual SUPREMA
11. Technical Data
11.2.15 MRO 10-16-TS Redundant Relais Output Unit (Rail-Mount Installation)
Order No.: 10021430
Function
- relay module, installed on mounting rail
- actuated by 2 MGO modules
- relays locked via the MRC module (LOCK)
- switching status display (green LED, made = ON)
- series connection of 2 contacts
- connection across 2 terminals
- contacts closed = status good
Technical Data
Relay operating voltage: 19 ... 32 VDC
Relay operating current: 7 mA
Contact type: normally open
Contact load capacity: see relay contact data
Temperature range: 5 °C ... 40 °C
Humidity: 0 ... 90 % relative humidity
noncondensing
Dimensions: 90 x 103 x 65 mm
Weight: 201 g
11.2.16 Relay Contact Data
Maximum switching voltage: 400 VAC
300 VDC
Nominal current: 3 A
Maximum switching power:
- a.c. voltage: 1500 VA
- d.c. voltage 24 VDC/3 A
(from load limit curve) 50 VDC/0.3 A
100 VDC/0.1 A
11.2.17 MAO 10 Analog Output Unit
Order No.: 10021050
Function
- 4 ... 20 mA output driver, measurement signal outputs
- optionally with electrically isolated outputs
- data transmission via the CAN bus
Technical Data
Operating voltage feed: 19.2 ... 32 V
Operating current: 150 mA (maximum)
Temperature range: 5 °C ... 40 °C