EasyManua.ls Logo

MSA SUPREMA - MRO 10-16-TS Redundant Relais Output Unit (Rail-Mount Installation); Relay Contact Data; MAO 10 Analog Output Unit

MSA SUPREMA
387 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
REV 0, June 1005 Page 243
Operation Manual SUPREMA
11. Technical Data
11.2.15 MRO 10-16-TS Redundant Relais Output Unit (Rail-Mount Installation)
Order No.: 10021430
Function
- relay module, installed on mounting rail
- actuated by 2 MGO modules
- relays locked via the MRC module (LOCK)
- switching status display (green LED, made = ON)
- series connection of 2 contacts
- connection across 2 terminals
- contacts closed = status good
Technical Data
Relay operating voltage: 19 ... 32 VDC
Relay operating current: 7 mA
Contact type: normally open
Contact load capacity: see relay contact data
Temperature range: 5 °C ... 40 °C
Humidity: 0 ... 90 % relative humidity
noncondensing
Dimensions: 90 x 103 x 65 mm
Weight: 201 g
11.2.16 Relay Contact Data
Maximum switching voltage: 400 VAC
300 VDC
Nominal current: 3 A
Maximum switching power:
- a.c. voltage: 1500 VA
- d.c. voltage 24 VDC/3 A
(from load limit curve) 50 VDC/0.3 A
100 VDC/0.1 A
11.2.17 MAO 10 Analog Output Unit
Order No.: 10021050
Function
- 4 ... 20 mA output driver, measurement signal outputs
- optionally with electrically isolated outputs
- data transmission via the CAN bus
Technical Data
Operating voltage feed: 19.2 ... 32 V
Operating current: 150 mA (maximum)
Temperature range: 5 °C ... 40 °C

Table of Contents