AFTER REPAIR Carry out a full check with the diagnostic tool.
V1
MR-453-X79-62C000$080.mif
CLIMATE CONTROL
Fault finding – Fault finding chart
62C
ALP 4
CONTINUED
Check that the condensation evacuation port (water from the evaporator) is not blocked.
Repair if necessary.
Is it an air distribution fault? See ALP 2.
Is it an air flow fault? See ALP 3.
Is it a heating performance fault?
See 61A, Heating, Fault finding chart, ALP 6 No
heating or insufficient heating.
Check that the recirculation flap is in the exterior air position.
Repair if necessary (see MR 451, Mechanical, 61A, Heating, Recirculation control cable: Removal - Refitting).
A
YES
NO
YES
NO
YES
NO