EasyManua.ls Logo

RFL Electronics RFL 9300 - Page 106

RFL Electronics RFL 9300
553 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RFL 9300 RFL Electronics Inc.
August 9, 2001 4 - 7 (973) 334-3100
4.2.6 FD PHASE - PHASE FAULT DETECTOR
Parameter #25 (FD PHASE) controls the local phase overcurrent fault detector. It can be set to
either 6 amperes or 8 amperes. It should be set above the maximum expected load, with a 10
to 15-percent safety margin. 6 amperes will be suitable for most applications. The phase over-
current fault detector is triggered when the peak true CT current value exceeds the peak value
of the setting i.e. 8.5A pk for a 6Arms setting and 11.25A for a 8Arms setting.
A high fault detector current setting does not compromise sensitivity, because the steady-state
fault detector is supplemented by several current-change fault detectors that are very sensitive.
The fault detectors are always monitoring the true CT current regardless of whether the relay is
configured for 2-terminal or 3-terminal operation. These detectors require no settings, and in-
clude the following:
o Peak Change
o Pulse-Width Change
o Slope Change
o Polarity Change
4.2.7 FD GND - GROUND FAULT DETECTOR
Parameter #26 (FD GND) controls the local ground overcurrent fault detector current. It can be
set to either 0.5 amperes or 1.0 amperes. It should be set above the maximum expected 3I
0
due to unbalanced load. 0.5 amperes will be suitable for most applications. The ground overcur-
rent fault detector monitors the integral value of the true CT current in order to de-sensitize its
response to transients.

Table of Contents