RFL 9300 RFL Electronics Inc.
January 30, 2002 6-18 (973) 334-3100
There are two methods for displaying parameters once you are in the READ mode. The first method is to press
and hold the [ENT] key to scroll automatically through the parameter list shown in Table 6-5 or 6-6 (as applica-
ble). If you go too far, you can press the [9] key to scroll back through the parameter list.
The second method is to manually enter the parameter number listed in Table 6-5 or 6-6 (as applicable). For
example, if you want to display the remote phase bias parameter, proceed as follows:
1. Press the [.] key to access the keypad.
2. Press the [5], [3], and [ENT] keys to select Parameter #53 ("R1 PH BS" - Remote 1 Phase Bias).
The parameter name ("R1 PH BS") will appear on the top line of the display, with the bias
setting listed on the bottom line.
3. If you would like to display the next parameter (Parameter #54, "R1 GD BS" - Remote 1 Ground Bias),
press the [ENT] key.
The parameter name ("R1 GD BS") will appear on the top line of the display, with the
bias level listed on the bottom line.