RFL 9300 RFL Electronics Inc.
January 30, 2002 6-22 (973) 334-3100
Table 6-6 continued. READ mode parameters for RFL 9300 Three-Terminal Charge Comparison Systems
41 CM ALM D Communications alarm delay. Programmable; see table 6-10 for more information.
43 DEFAULT Re-program to factory default values. Programmable; see table 6-10 for more information. (4)
44 BEEPER Enable/disable audible beeper. Programmable; see table 6-10 for more information. (5)
45 DISPLAY Adjust display intensity. Programmable; see table 6-10 for more information. (6)
46 XMT ADD1 Transmit address to remote 1. Programmable; see table 6-10 for more information.
47 XMT ADD2 Transmit address to remote 2. Programmable; see table 6-10 for more information.
50 G B4 TRP Enable/disable guard before trip. Programmable; see table 6-10 for more information.
51 RS232 BD Selects RS-232 baud rate. Programmable; see table 6-10 for more information.
52 RS232PR Selects RS-232 handshaking protocol. Programmable; see table 6-10 for more information.
53 R1 PH BS Remote 1 phase bias.
54 R1 GD BS Remote 1 ground bias.
55 R1 BS CL Remote 1 bias control.
56 R1 GD DY Remote 1 ground delay action.
57 R1 DLY S Remote 1 time delay.
58 R1 FD PH Remote 1 fault detector phase current.
59 R1 FD GD Remote 1 fault detector ground current.
60 R1 BCKUP Remote 1 backup functions.
61 R1 PH OC Remote 1 phase overcurrent backup.
62 R1 GD OC Remote 1 ground overcurrent backup.
63 R1 P TOC Remote 1 phase inverse time-overcurrent backup.
64 R1 PPKUP Remote 1 phase inverse time-overcurrent pickup value.
65 R1 PCURV Remote 1 phase inverse time-overcurrent curve select value.
66 R1 PDIAL Remote 1 phase inverse time-overcurrent dial setting value.
67 R1 G TOC Remote 1 ground inverse time-overcurrent backup.
68 R1 GPKUP Remote 1 ground inverse time-overcurrent pickup value.
69 R1 GCURV Remote 1 ground inverse time-overcurrent curve select value.
70 R1 GDIAL Remote 1 ground inverse time-overcurrent dial setting value.
71 R1 OH/UG Remote 1 overhead or underground.
72 R1 OP/CN Remote 1 open conductor action. (7)
73 R1 STUB Remote 1 stub bus action.
75 R1 GD TP Remote 1 guard before trip.
76 R1 PNGPG Remote 1 ping-pong (round-trip delay).
78 R2 PH BS Remote 2 phase bias.
79 R2 GD BS Remote 2 ground bias.
80 R2 BS CL Remote 2 bias control.
81 R2 GD DY Remote 2 ground delay action.
82 R2 DLY S Remote 2 time delay.
>> Table continues on next page <<
>> Refer to page 6-24 for notes <<