091 - R2 Ph TOC Dial Remote 2 Phase Inverse Time-overcurrent Dial setting. Refer to note 6 on page
6-28 for settings.
092 - R2 Ground TOC Remote 2 Ground Inverse Time-overcurrent function. Can be enabled or dis-
abled. See note below.
093 - R2 Gd TOC Pickup Remote 2 Ground Inverse Time-overcurrent Pickup value. Can be set from 0.5
to 31.0 amperes in 0.125 ampere steps.
094 - R2 Gd TOC Curve Remote 2 Ground Inverse Time-overcurrent Curve select. Refer to note 7 on
page 6-28 for settings.
095 - R2 Gd TOC Dial Remote 2 Ground Inverse Time-overcurrent Dial setting. Refer to note 7 on
page 6-28 for settings.
096 - R2 Overhd/Undrgd Remote 2 Overhead or Underground cables.
097 - R2 Open Cond Remote 2 Open Conductor. Can be set to alarm or trip.
098 - R2 Stub Bus Remote 2 Stub Bus status. Can be active or inactive (not programmable).
100 - R2 Guard/Trip Remote 2 Guard before Trip. Can be set to enable or disable.
101 - R2 PingPong Remote 2 PingPong Delay in ms from local to remote 2 as measured by remote
2.
160 - R1 Single-Pole Single-pole status at remote 1. Can be active or inactive. (Jumper selectable
using jumper J5 on 93B SV at remote 1)
161 - R1 Selective Pole Selective pole relaying status at remote 1. Can be enabled or disabled. This
parameter is only available when single-pole trip is active.
165 - R1 Trip Release Code Determines algorithm used by the Display Controller at remote 1 to determine
when output trip signal should be unlatched. Three algorithms are available
See note 11 on page 6-30 for details.
180 - R2 Single Pole Single-pole status at remote 2. Can be active or inactive. (Jumper selectable
using jumper J5 on 93B SV at remote 2)
181 - R2 Selective Pole Selective pole relaying status at remote 2. Can be enabled or disabled. This
parameter is only available when single-pole trip is active.
185 - R2 Trip Release Code Determines algorithm used by the Display Controller at remote 2 to determine
when output trip signal should be unlatched. Three algorithms are available
See note 11 on page 6-30 for details.
NOTE
If parameter No. 088 is disabled, then parameter numbers 090 and 091 will display N/A (not applicable).
If parameter No. 092 is disabled, then parameter numbers 094 and 095 will display N/A (not applicable).
RFL 9300 RFL Electronics Inc.
January 30, 2002 6-50 (973) 334-3100