071 - R1 Overhd/Undrgd Remote 1 Overhead or Underground cables.
072 - R1 Open Cond Remote 1 Open Conductor. Can be set to alarm or trip.
073 - R1 Stub Bus Remote 1 Stub Bus status. Can be active or inactive (not programmable).
074 - R1 DC Offset Flt Remote 1 DC Offset Filter. Can be set to enable or disable.
075 - R1 Guard/Trip Remote 1 Guard before Trip. Can be set to enable or disable.
076 - R1 PingPong Remote 1 PingPong Delay in ms from local to remote 1 as measured by remote
1.
077 - R1 CDC Remote 1 Channel Delay Compensation in ms.
078 - R2 Phase Bias Remote 2 Phase Bias setting in amperes. Can be set from 1.0 to 8.0 amperes
in 0.5 ampere steps.
079 - R2 Ground Bias Remote 2 Ground Bias setting in amperes. Can be set from 1.0 to 2.25 am-
peres in 0.25 ampere steps.
080 - R2 Bias Control Remote 2 Bias Control. Can be enabled or disabled.
081 - R2 Ground Delay Remote 2 Ground Delay function. Can be enabled or disabled.
082 - R2 Bias/Gnd Dly Remote 2 Bias Control and Ground Delay time.
083 - R2 FD Phase Remote 2 Phase Overcurrent Fault Detector. Can be set to 6.0 or 8.0 amperes.
084 - R2 FD Ground Remote 2 Ground Overcurrent Fault Detector current. Can be set to 0.5 or 1.0
amperes.
085 - R2 Backup Remote 2 System Backup functions. Can be enabled or disabled.
086 - R2 Ph O/C Bkup Remote 2 Phase Overcurrent Backup function. Can be set from 6.0 to 31.875
amperes in 0.125 ampere steps.
087 - R2 Gnd O/C Bkup Remote 2 Ground Overcurrent Backup function. Can be set from 6.0 to 31.875
amperes in 0.125 ampere steps.
088 - R2 Phase TOC Remote 2 Phase Inverse Time-overcurrent function. Can be enabled or dis-
abled. See note below.
089 - R2 Ph TOC Pickup Remote 2 Phase Inverse Time-overcurrent Pickup value. Can be set from 0.5
to 31.875 amperes in 0.125 ampere steps.
090 - R2 Ph TOC Curve Remote 2 Phase Inverse Time-overcurrent Curve select. Refer to note 6 on
page 6-28 for settings.