EasyManua.ls Logo

Schweitzer Engineering Laboratories SEL-421-4 - Page 1331

Schweitzer Engineering Laboratories SEL-421-4
1518 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16.15
Date Code 20171006 Instruction Manual SEL-400 Series Relays
DNP3 Communication
DNP3 Documentation
23 5 32-Bit frozen counter event with time
23 6 16-Bit frozen counter event with time
23 7 32-Bit frozen delta counter event with time
23 8 16-Bit frozen delta counter event with time
30 0 Analog input—All variations 1 0, 1, 6, 7, 8,
17, 28
30 1
b
32-Bit analog input with flag 1 0, 1, 6, 7, 8,
17, 28
129 0, 1, 17, 28
30 2
b
16-Bit analog input with flag 1 0, 1, 6, 7, 8,
17, 28
129, 130 0, 1, 17, 28
30 3
b
32-Bit analog input without flag 1 0, 1, 6, 7, 8,
17, 28
129 0, 1, 17, 28
30 4
b
16-Bit analog input without flag 1 0, 1, 6, 7, 8,
17, 28
129 0, 1, 17, 28
30 5
b
Single-precision floating point analog input with flag 1 0, 1, 6, 7, 8,
17, 28
129 0, 1, 17, 28
30 6
b
Double-precision floating point analog input with flag 1 0, 1, 6, 7, 8,
17, 28
129 0, 1, 17, 28
31 0 Frozen analog input—All variations
31 1 32-Bit frozen analog input
31 2 16-Bit frozen analog input
31 3 32-Bit frozen analog input with time of freeze
31 4 16-Bit frozen analog input with time of freeze
31 5 32-Bit frozen analog input without flag
31 6 16-Bit frozen analog input without flag
32 0 Analog change event—All variations 1 6, 7, 8
32 1
b
32-Bit analog change event without time 1 6, 7, 8 129 17, 28
32 2
b
16-Bit analog change event without time 1 6, 7, 8 129, 130 17, 28
32 3 32-Bit analog change event with time 1 6, 7, 8 129 17, 28
32 4 16-Bit analog change event with time 1 6, 7, 8 129 17, 28
32 5
b
Single-precision floating point analog change event with-
out time
1 6, 7, 8 129 17, 18
32 6
b
Double-precision floating point analog change event
without time
1 6, 7, 8 129 17, 18
32 7
b
Single-precision floating point analog change event with
time
1 6, 7, 8 129 17, 28
32 8
b
Double-precision floating point analog change event with
time
1 6, 7, 8 129 17, 28
33 0 Frozen analog event—All variations
33 1 32-Bit frozen analog event without time
33 2 16-Bit frozen analog event without time
33 3 32-Bit frozen analog event with time
33 4 16-Bit frozen analog event with time
Table 16.8 Relay DNP3 Object List (Sheet 4 of 6)
Obj. Var. Description
Request
a
Response
a
Funct. Codes Qual. Codes Funct. Codes Qual. Codes

Table of Contents