2.7
Date Code 20171006 Instruction Manual SEL-400 Series Relays
PC Software
Settings Database Management and Drivers
Drivers
Relay settings folders in QuickSet are closely associated with the QuickSet relay
driver that you used to create the settings. The relay settings and the QuickSet
drivers must match.
Step 1. Use one of the following methods to view the relay FID (firmware
identification) number to determine the active QuickSet drivers.
➢ Enter Access Level 1 and use the STATUS command from the
serial port terminal emulation window.
➢ Type ID <Enter> in the computer emulation software window
(<Ctrl+T> from QuickSet).
Step 2. Locate and record the Z-number in the FID string.
The Z-number helps determine the proper QuickSet relay settings
driver version when creating or editing relay settings files.
Step 3. View the QuickSet settings driver information at the bottom of the
Settings Editor window.
The first portion of the Z-number is the QuickSet settings driver
version number (see Figure 2.4).
Step 4. Compare the QuickSet driver number and the relay FID number.
This QuickSet driver Z-number and the corresponding part of the
relay FID must match.
Use the first portion of the Z-number (Z001XXX, for example) to
determine the correct Settings Editor version to select.
Step 5. View the top of the Settings Editor window to check the Settings
Editor driver number (see Figure 2.5).
Figure 2.4 QuickSet Software Driver Information in the FID String
FID = SEL-487B-1-R306-V0-Z007005-D20130606
Relay Settings Driver Version Number
HMI Version Number