EasyManua.ls Logo

Allen-Bradley Kinetix 5100 2198-E1004-ERS - Configuring Homing Setting ID397 (P6.000)

Allen-Bradley Kinetix 5100 2198-E1004-ERS
500 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 2198-UM004A-EN-P - October 2019 257
Motion Control in PR Mode Chapter 11
Definition of each setting value:
Configuring Homing Setting ID397 (P6.000)
Settings:
ZY X
Limit setting Z pulse setting Homing method
-
Y = 0: return to Z pulse
Y = 1: go forward to Z pulse
Y = 2: do not look for Z pulse
X = 0: homing in forward direction and define PL as
homing origin
X = 1: homing in reverse direction and define NL as
homing origin
When encounter limit:
Z = 0: show error
Z = 1: reverse direction
X = 2: homing in forward direction, ORG: OFFON as
homing origin
X = 3: homing in reverse direction, ORG: OFFON as
homing origin
-
X = 4: look for Z pulse in forward direction and define it as
homing origin
X = 5: look for Z pulse in reverse direction and define it as
homing origin
Y = 0: return to Z pulse
Y = 1: go forward to Z pulse
Y = 2: do not look for Z pulse
X = 6: homing in forward direction, ORG: ONOFF as
homing origin
X = 7: homing in reverse direction, ORG: ONOFF as
homing origin
-
-
X = 8: define current position as the origin
Y = 0: return to Z pulse
Y = 2: do not look for Z pulse
X = 9: look for the collision point in forward direction and
define it as the origin
X = A: look for the collision point in reverse direction and
define it as the origin
A DEC2: deceleration time selection of second homing YX CMD: command type
B DLY: select 0…F for delay time Z ACC: select 0…F for acceleration time
C N/A U DEC1: deceleration time selection of first homing
D BOOT - -
BCD
A
YXZU

Table of Contents

Related product manuals