380 Rockwell Automation Publication 2198-UM004A-EN-P - October 2019
Chapter 13 Kinetix 5100 Safe Torque Off (STO) Feature
Figure 193 - Typical Fault Reset Sequence
For Safety Status (SS), you can configure one parameter/attribute, ID252
(P2.093) STOFeedbackConfiguration and determine whether SS will latch, if an
STO fault occurs. If SS signal is latched when STO fault occurs, the status of SS
signal remains even when the fault has been cleared.
Figure 194 - Parameter Format Legend
Table 111 - SS Signal Status/Behavior for STO Faults
24V DC
24V DC
0V DC
0V DC
1
0
10 ms
1
0
STO Fault Code E 500
STO_A (S1)
STO_B (S2)
Fault Reset Command
IMPORTANT The STO fault (E 500) can be reset only if both inputs are in the ON state. After
the fault reset requirement is satisfied, a Fault Reset command in the
application software or DI.ARST (physical input) must be issued to reset the
E 500 fault. You can reset faults E 501, E 502, and E 503 with power cycle.
Servo Drive Status SS Signal Status
(1)
(1) Open indicates continuity between SS+ and SS– is open circuit. Close indicates continuity between SS+ and SS– is short circuit.
Parameter ID252 (P2.093) XX1X XX2X
SS signal behavior No latch Latch
No STO fault occurs Open
STO fault occurs
E 500 Close
E 501 Open
E 502 Open
E 503 Open
P2.093 = XX. 0 X
Reserved
Latch Status
1 = SS no latch
2 = SS latch
Reserved