Rockwell Automation Publication 2198-UM004A-EN-P - October 2019 99
Use the Keypad Interface Chapter 5
Drive Status Display
This display provides drive information and access to the Setting display, which
shows network and parameter information. When the drive is enabled/servo on,
the information can only be viewed.
Use the keys to move between status information displays.
24
Monitor variable number 2 displays the content of
parameter ID664 (P0.010). Specify the monitor variable
code by using ID669 (P0.018).
—
25
Monitor variable number 3 displays the content of
parameter ID665 (P0.011). Specify the monitoring
variable code by using ID670 (P0.019).
—
26
Monitor variable number 4 displays the content of
parameter ID666 (P0.012). Specify the monitoring
variable code by using ID667 (P0.020).
—
27
Offset value between motor position and Z phase in PUU
unit. The value is 0 when the position overlaps with Z
phase. The greater the value, the greater the offset.
User Unit
28
Current drive fault. —
Table 59 - Real Time Display Symbols (Continued)
Code
Real Time Displayed
Symbol Description Unit
Drive
Status
Device
Information
Version
Information
Setting
Information Display/Setup Mode