Rockwell Automation Publication 2198-UM004A-EN-P - October 2019 53
Connector Data and Feature Descriptions Chapter 3
Analog Inputs
There are two analog inputs, COMMAND1 and COMMAND2, available on
the I/O connector.
Table 30 - Analog Input Specifications
Figure 28 - Analog COMMAND Input Configuration
Pulse Inputs
There are two pulse inputs available on the 2198-TBIO connector. They support
either single-ended or differential pulse signals by wiring differently. For single-
ended signals, they can be wired as current sinking (NPN) or sourcing (PNP)
inputs.
Figure 29 - Pulse Input - Single-ended Configuration (current sourcing)
Parameter Description
Analog inputs voltage –10 V… +10 Vs
Analog inputs resolution 11 bits, min
Analog inputs scan time 0.0625 ms, max
Analog inputs impedance 12 kΩ typical, approx.
AGND
±10V
10 kΩ
13
18
42
COMMAND1-Torque
COMMAND2-Speed
Analog GND
Servo Drive
Controller
I/O Connector with
2198-TBIO Expansion Block
DC
24V
1.5 KΩ
51 Ω
51 Ω
51 Ω
1.5 KΩ
Puls e i nput frequency (max):
200 kHz
51 Ω
35
39
37
41
Puls e i nput frequency (max):
200 kHz
43
36
Pulse B+
BPWR
Pulse B–
APWR
Pulse A+
Pulse A–
Servo Drive
Controller
I/O Connector with
2198-TBIO Expansion Block