38 Rockwell Automation Publication 2198-UM004A-EN-P - October 2019
Chapter 2 Plan and Install the Kinetix 5100 Drive System
Mount the Drive
Follow these steps to mount your Kinetix 5100 drive.
1. Lay out the position for the Kinetix 5100 drive and accessories in the
enclosure.
See Establish Noise Zones
on page 33 for panel layout recommendations.
2. Drill holes in the panel for mounting your servo drive.
Refer to Drill-hole Patterns
on page 37. For drive dimensions, see the
Kinetix Servo Drives Specifications Technical Data, publication
KNX-TD003
.
3. Loosely attach the servo drive to the panel.
The recommended mounting hardware is M4 (#8-32) steel machine
screws. Observe bonding techniques as described in Bonding Drives
on
page 30
.
4. Tighten all mounting fasteners.
5. Apply 2.0 N•m (17.7 lb•in) maximum torque to each fastener.
IMPORTANT To improve the bond between the Kinetix 5100 drive and subpanel,
construct your subpanel out of zinc-plated (paint-free) steel.