Appendix B Upgrade the Drive Firmware
Before You Begin
The firmware revision for software must be as shown for EtherNet/IP™ networks.
Table 135 - Kinetix 5100 System Requirements
Description Firmware Revision
Logix Designer application 30.00.00 or later
RSLinx® software 3.60.00 or later
ControlFLASH software kit
(1)
(1) Download the ControlFLASH kit from http://support.rockwellautomation.com/controlflash. Contact Rockwell Automation Technical
Support at (440) 646-5800 for assistance.
For more ControlFLASH information (not drive specific), see the ControlFLASH Firmware Upgrade Software User Manual, publication
1756-UM105
.
14.01.00 or later
Catalog numbers of the targeted Kinetix 5100 drive that you want to upgrade.
Network path to the targeted Kinetix 5100 drive that you want to upgrade.
IMPORTANTIMPORTANT Control power must be present at L1 (110/230V AC+) and L2 (110/230V AC-)
prior to upgrading your target module.
IMPORTANT The state on the display must be STDBY (STANDBY) in IO mode before
upgrading your target module.
The state on the display must be STOP (STOPPED) in other modes before
upgrading your target module.
ATTENTION: To avoid personal injury or damage to equipment during the
firmware upgrade due to unpredictable motor activity, do not apply the main
power to the drive. Do apply the control power to the drive.