104 01-6203-01R3, CG Drives & Automation
Manual loading of the OEM data via device command
Device command: "Load OEM data" 0x2022:005 (P700.05)
• If the OEM memory contains invalid parameter settings, the user parameter settings
are loaded automatically.
• If the OEM memory is empty, the status feedback "Action cancelled" takes place. The
current parameter settings remain unchanged.
Manual saving of the parameter settings via device command
Device command: "Save user data" 0x2022:003 (P700.03)
• It may happen that the parameter settings cannot be saved because the user memory
is full. In this case, the following error message appears:
module is full
The memory module contains too many parameter settings. The inverter copies the current backup to the user memory
without overwriting the data in the RAM.
Remedy: Execute device command "Save user data" 0x2022:003 (P700.03) again. This reinitialises the user memory with
the current parameter settings. By this means, parameter settings no longer required are deleted automatically.