260 01-6203-01R3, CG Drives & Automation
10.1.2. Saving/loading the parameter settings
If parameter settings of the inverter are changed, these changes at first are only made in
the RAM memory of the inverter. In order to save the parameter settings with mains
failure protection, the inverter is provided with a pluggable memory module and
corresponding device commands.
Details
The memory module is provided with two memories, the user memory and the OEM
memory.
User memory
The user memory is used as power-failure-proof storage of parameter settings made by
the user during commissioning/operation.
The SET display is blinking on the keypad if a parameter setting has been changed but
has
not been saved in the memory module with mains failure protection. In order to
save parameter settings in the user memory of the memory module, press the keypad
"Enter" key > 3 s.
Parameter settings carried out with »Emotron Easy starter« or via network must be
explicitly saved in the user memory by means of the "Save user data" device
command, so that the changes carried out are not lost when the mains of the inverter
are switched.
Saving can also be made in the »Emotron Easy starter« via the button
or the <F6>
function key.
The device command "Load user data" serves to reload the data from the user memory
into the RAM.

Table of Contents

Other manuals for Emotron VS10

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emotron VS10 and is the answer not in the manual?

Emotron VS10 Specifications

General IconGeneral
BrandEmotron
ModelVS10
CategoryController
LanguageEnglish

Related product manuals