10.1.2.1. 10.1.3 Device commands for parameter change-over
The inverter supports several parameter sets. The parameter set can be selected by
means of the device commands "Load parameter set 1" ... "Load parameter set 4".
DANGER!
Changed parameter settings can become effective immediately depending on the
activating method set in 0x4046 (P755.00).
The possible consequence is an unexpected response of the motor shaft while the inverter
is enabled.
If possible, only carry out parameter changes while the inverter is disabled.
Certain device commands or settings which might cause a critical state of the drive behaviour can generally only be
carried our when the inverter is inhibited.
Details
The "parameter change-over" function provides a change-over between four sets with
different parameter values for up to 32 freely selectable parameters. For details on the
compilation of the parameters and setting of the value sets, see the chapter "Parameter
change-over".
The change-over via the device commands depends on the activation method set in
0x4046 (P755.00):
Activation method = 1 or 3: Change-over takes place immediately.
Activation method = 0 or 2: The respective device command is only executed if the
inverter is disabled.
Parameter
Name / value range / [default setting]
Info
0x2022:007
(P700.07)
Device commands: Load parameter set 1
(Device commands: Load par. set 1)
For further possible settings, see parameter
0x2022:001 (P700.01).
242
1 = load value set 1 of the "Parameter change-over" function.
The parameters specified in 0x4041/1...32 are set to the values set in
0x4042/1...32.
After successful execution, the value 0 is shown.
Parameter change-over
285
0
Off / ready
Only status feedback
0x2022:008
(P700.08)
Device commands: Load parameter set 2
(Device commands: Load par. set 2)
For further possible settings, see parameter
0x2022:001 (P700.01).
242
1 = load value set 2 of the "Parameter change-over" function.
The parameters specified in 0x4041/1...32 are set to the values set in
0x4043/1...32.
After successful execution, the value 0 is shown.
Parameter change-over
285
0
Off / ready
Only status feedback
0x2022:009
(P700.09)
Device commands: Load parameter set 3
(Device commands: Load par. set 3)
For further possible settings, see parameter
0x2022:001 (P700.01).
242
1 = load value set 3 of the "Parameter change-over" function.
The parameters specified in 0x4041/1...32 are set to the values set in
0x4044/1...32.
After successful execution, the value 0 is shown.
Parameter change-over
285
0
Off / ready
Only status feedback
0x2022:010
(P700.10)
Device commands: Load parameter set 4
(Device commands: Load par. set 4)
For further possible settings, see parameter
0x2022:001 (P700.01).
242
1 = load value set 4 of the "Parameter change-over" function.
The parameters specified in 0x4041/1...32 are set to the values set in
0x4045/1...32.
After successful execution, the value 0 is shown.
Parameter change-over
285
0
Off / ready
Only status feedback