10.2. Keypad
For the keypad various settings can be made, which are described in detail in the following
subchapters.
10.2.1. Keypad language selection
Name / value range / [default setting]
(P705.00)
Keypad language selection
(KP language)
Language selection for the keypad display.
10.2.2. Keypad setpoint increment
Name / value range / [default setting]
(P701.00)
Keypad setpoint increment
(KP setp. incr.)
1 ... [1] ... 100
Adaptation of the increment for keypad setpoints when a keypad arrow
key is pressed once. The value set serves as a multiplier for the preset
increments.
Preset increments:
0.1 Hz for frequency setpoint 0x2601:001 (P202.01).
0.01 PUnit for process controller setpoint 0x2601:002 (P202.02).
•
1 % for torque setpoint 0x2601:003 (P202.03).
Notes:
With a setting > 1, the option of repeatedly changing the setpoint by
pressing the key for a longer time is deactivated.
The setting only has an impact on the keypad setpoints.
Example: with the setting "5", the keypad frequency setpoint is
increased/decreased by 0.5 Hz every time the key is pressed.
10.2.3. Keypad scaling of speed display
Name / value range / [default setting]
0x4002
(P702.00)
Speed display scaling
(Scal.speed fact.)
0.00 ... [0.00] ... 650.00
Factor for the scaling of the speed display in 0x400D (P101.00).
With the setting "0.00", no scaling takes place.
Example: with the "16.50" and the actual frequency = 50 Hz, 0x400D
(P101.00) shows the speed "825 rpm".
(P101.00)
(Scaled act value)
Display of the current speed in application units.
10.2.4. Keypad status display
During operation, the keypad displays the output frequency of the inverter, or with an
active PID control it shows the process controller setpoint. Alternatively, an optional
diagnostic parameter can be displayed during operation.
Name / value range / [default setting]
(P703.00)
(KP status displ.)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
0 = normal display depending on the operating mode
In case of an active frequency control, the keypad displays the output
frequency of the inverter.
In case of active PID control, the keypad displays the current Process
controller setpoint in [P-Unit].
As an alternative, an optional diagnostic parameter can be set here,
which is to be shown on the keypad during operation.
Format: 0xiiiiss00 (iiii = hexadecimal index, ss = hexadecimal subindex)
The lowest byte is always 0x00.
The keypad can be used to select the desired diagnostics parameter