164 01-6203-01R3, CG Drives & Automation
7.4.4.6. Flying restart controller
For a quick commissioning, the calculations and settings are made automatically during
the optimisation.
Details
The following parameter is only relevant for the flying restart circuit if an asynchronous
motor is controlled. In case of a sensorless control of a synchronous motor (SL-PSM) the
parameter has no meaning.
Name / value range / [default setting]
0x2BA1:003
(P718.03)
Flying restart circuit: Restart time
(Flying restart: Restart time)
1 ... [5911]* ... 60000 ms
* Default setting depending on the size.
Integration time for controlling the flying restart circuit.
7.4.4.7. SLVC controller
For a quick commissioning, the calculations and settings are made automatically during
the optimisation.
Preconditions
The SLVC controller is only effective in the motor control type "Sensorless vector control
(SLVC)".
Name / value range / [default setting]
0.0000 ... [0.2686]* ... 1000.0000 Hz/A
* Default setting depending on the size.
Gain of the SLVC-Q controller.
1.0 ... [2.3]* ... 2000.0 ms
* Default setting depending on the size.
Reset time of the SLVC-Q controller.