13.1.4. Environmental conditions
Reference: Factory setting (switching frequency 8 kHz variable)
2K3 (-25 ... +70 °C)
EN 60721-3-2
Transport
Operation at a switching frequency of 2 or 4 kHz: above +45°C,
reduce rated output current by 2.5 %/°C
Operation at a switching frequency of 8 or 16 kHz: above +40°C,
reduce rated output current by 2.5 %/°C
Reduce rated output current by 5 %/1000 m
Pollution
operation
13.1.5. Electrical supply conditions
Permissible mains systems
Voltage to earth/ground: max. 300 V
IT
Apply the measures described for IT systems!
IT systems are not relevant for UL-approved systems