446 01-6203-01R3, CG Drives & Automation
12.14.1.1. Example 1: Input range 0 ... 10 V ≡ setting range 0 ... 50 Hz
In this configuration, for instance, a frequency setpoint between 0 and 50 Hz can be set
with a potentiometer connected to the analog input.
Parameter
Name
Setting for this example
Analog input 1: Input range
Analog input 1: Min frequency value
Analog input 1: Max frequency value
Analog input 1: Filter time
12.14.1.2. Example 2: Input range 0 ... 10 V ≡ setting range -40 ... +40 Hz
In this example, a bipolar setting range and a dead band with 2 % are configured.
Analog input 1: Input range
0x2636:002 (P430.02)
Analog input 1: Min frequency value
-40.0 Hz
Analog input 1: Max frequency value
Analog input 1: Filter time
Analog input 1: Dead band
Frequency
setpoint
selection
(Input voltage
1 V ≡ 5 Hz)