2.2. Residual hazards
The user must take the residual hazards mentioned into consideration in the risk
assessment for his/her machine/system.
If the above is disregarded, this can lead to severe injuries to persons and damage to
material assets!
Product
Observe the warning labels on the product!
Icon Description
Electrostatic sensitive devices:
Before working on the product, the staff must ensure to be free of electrostatic charge!
Dangerous electrical voltage
Before working on the product, check if no voltage is applied to the power terminals!
After mains disconnection, the power terminals carry the hazardous electrical voltage given on the product!
High leakage current:
Carry out fixed installation and PE connection in compliance with EN 61800−5−1 or EN 60204−1!
Hot surface:
Use personal protective equipment or wait until devices have cooled down!
Motor
If there is a short circuit of two power transistors, a residual movement of up to
180°/number of pole pairs can occur at the motor! (For 4-pole motor: residual movement
max. 180°/2 = 90°).
2.3. Application as directed
The product must only be operated under the operating conditions prescribed in this
documentation.
The product meets the protection requirements of 2014/35/EU: Low-Voltage Directive.
The product is not a machine in terms of 2006/42/EC: Machinery Directive.
Commissioning or starting the operation as directed of a machine with the product is
not permitted until it has been ensured that the machine meets the regulations of the
EC Directive 2006/42/EC: Machinery Directive; observe EN 60204−1.
Commissioning or starting the operation as directed is only allowed when there is
compliance with the EMC Directive 2014/30/EU.
The harmonised standard EN 61800−5−1 is used for the inverters.
The product is not a household appliance, but is only designed as component for
commercial or professional use in terms of EN 61000−3−2.
The product can be used according to the technical data if drive systems have to
comply with categories according to EN 61800−3.
In residential areas, the product may cause EMC interferences. The operator is
responsible for taking interference suppression measures.

Table of Contents

Other manuals for Emotron VS10

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emotron VS10 and is the answer not in the manual?

Emotron VS10 Specifications

General IconGeneral
BrandEmotron
ModelVS10
CategoryController
LanguageEnglish

Related product manuals