12.2.4. Example 4: Quick stop
This example illustrates the "quick stop" function. If quick stop is activated, the motor is
brought to a standstill within the deceleration time set in 0x291C (P225.00).
Switch S1 starts the motor in forward direction of rotation. Switch S1 in the initial
position stops the motor again.
Switch S2 activates the "quick stop" function.
Cancelling the quick stop causes a restart of the motor if "Run" is still active
(switch S1 closed)!
Connection plan
function
Potentiometer R1
Frequency setpoint selection
Switch S1
Run
Switch S2 Activate quick stop
Parameter
Name
Setting for this example
0x2631:001 (P400.01)
Enable inverter
Constant TRUE [1]
0x2631:002 (P400.02)
Run
Digital input 1 [11]
0x2631:003 (P400.03)
Activate quick stop
Digital input 2 [12]
0x2631:004 (P400.04)
Reset fault
Not connected [0]
0x2917 (P220.00)
Acceleration time 1
3.0 s
0x2918 (P221.00)
Deceleration time 1
3.0 s
0x291C (P225.00)
Quick stop deceleration time
1.0 s