The status signals can be assigned to digital outputs.
Configuration of digital outputs
429
① The "Run" functions serves as start enable for the functions "Run forward (CW)"
and "Run reverse (CCW)".
Without start enable, the motor cannot be started.
② If the start command is cancelled, the motor is stopped with the stop method set in
0x2838:003 (P203.03). In the example: Stop with standard ramp.
After a renewed start enable, the inverter waits for the next run command.
③ If, at start enable, either "Run forward (CW)" or "Run reverse (CCW)" is set to TRUE,
the motor starts into the triggered direction.
④ The inverter always responds to the run command detected last (if start enable is
available).
In the example, the "Run reverse (CCW)" command replaces the still active "Run
forward (CW)" command.
⑤ If, at start enable, both run commands are set to TRUE, the motor remains stopped
until only one valid run command is available
.