232 01-6203-01R3, CG Drives & Automation
8.5.13. Resetting the CANopen interface
The following parameter can be used to restart or stop communication. Optionally it is
also possible to reset all communication parameters to the default status.
Details
A restart of communication is required after changes of the interface configuration (e. g.
node address and baud rate) in order that the changed settings become effective.
For restarting communication, there are two options:
1. Switch inverter off and on again.
2. Set the selection = "Restart with current values [1]" in 0x2300 (P508.00).
Parameter
Name / value range / [default setting]
Info
0x2300
(P508.00)
CANopen communication
(CANopen comm.)
Setting can only be changed if the inverter is
inhibi
ted.
Restart / stop communication.
After successful execution, the value 0 is shown.
0
No action/no error
Only status feedback
1
Restart with current values
Restart communication with the current values.
2
Restart with default values
Restart communication with the standard values of the CAN parameters
(0x1000 ... 0x1FFF and 0x2301).
5
Stop network communication
Stop communication.
The "Stop Remote Node" NMT command is executed. After successful
execution of this command, only the reception of network
management frames is possible.
10
In progress
Only status feedback
11
Action cancelled
12
Error