96 01-6203-01R3, CG Drives & Automation
5.2.9. Sequencer diagnostics
The following parameters serve to diagnose the "sequencer" function.
Name / value range / [default setting]
0x2DAE:001
(P140.01)
Sequencer diagnostics: Active step
(Sequencer diag: Active Step)
Read only
Display of the active step.
0 ≡ no sequence active.
(P140.02)
Sequencer diagnostics: Step time elapsed
(Sequencer diag: StepTime elapsed)
Read only: x.x s
Display of the time that has passed since the start of the current step.
(P140.03)
Sequencer diagnostics: Step time remaining
(Sequencer diag: StepTime remain)
Read only: x.x s
Display of the residual time for the current step.
(P140.04)
Sequencer diagnostics: Steps complete
(Sequencer diag: Steps complete)
Read only
Display of the number of steps that have been made since the start of
the sequence.
(P140.05)
Sequencer diagnostics: Steps remaining
(Sequencer diag: Steps remain)
Read only
Display of the residual number of steps until the current sequence is
completed. This includes the current step.
(P140.06)
Sequencer diagnostics: Active sequence
(Sequencer diag: Active sequence)
Read only
Display of the active sequence.
0 ≡ no sequence active.
(P140.07)
Sequencer diagnostics: Active segment
(Sequencer diag: Active segment)
Read only
Display of the active segment.
0 ≡ no sequence active.
255 ≡ final sequence active.
0x2DAE:008
(P140.08)
Sequencer diagnostics: Relative sequence time
remaining
(Sequencer diag: SeqTime remain %)
Read only: x %
Display of the residual time of the sequence in [%].
(P140.09)
Sequencer diagnostics: Absolute sequence time
remaining
(Sequencer diag: SeqTime remain)
Read only: x.x s
Display of the residual time of the sequence in [s].
Related topics
Sequencer
327
Sequencer control functions
416