330 01-6203-01R3, CG Drives & Automation
10.14. Automatic restart
Configuration of the restart behaviour after a fault.
The settings have no impact on errors and warnings of the inverter.
Name / value range / [default setting]
0x2839:002
Fault configuration: Restart delay
If a fault occurs, a restart is possible at the earliest after the time set
(Fault config.: Restart delay)
0.0 ... [3.0] ... 1000.0 s
Fault configuration: Number of restart attempts
Number of restart attempts after a fault.
(Fault config.: Restart counter)
255 = unlimited number of restart attempts.
Fault configuration: Trouble counter reset time
Time of trouble-free operation after the expiry of which the fault coun-
(Fault config.: Tro.count r.time)
0.1 ... [5.0] ... 3600.0 s
0x2839:005
Fault configuration: Trouble counter
Display of the current fault counter content.
(Fault config.: Trouble counter)
The counter content is increased by 1 after each restart attempt.
Related topics
Error handling
84
Timeout für fault reaction
313